Font size:

lxw

 

LXW Series Hot-Water Boilers

Multiple water tube, Hot-water boiler. Miura’s natural gas/propane hot water boiler is a low water content, water tube design, which provides full output within 5 minutes.

  • Low-NOx Power Burner Design
  • Up to 175BHP per boiler

Specifications
ITEM LXW-50G LXW-100G LXW-150G LXW-175G
Boiler Type Multiple water tubes
Utilization Horsepower[1] 50 BHP 100 BHP 150 BHP 175 BHP
Maximum Pressure 160 PSIG
Heat Output 1,674,000 BTU/hr 3,348,000 BTU/hr 5,022,000 BTU/hr 5,859,000 BTU/hr
Efficiency[2] 82% 80%
Heating Surface Area 177 FT² 247 FT² 404 FT²
Operational Weight 3,200 LBS 4,650 LBS 5,800 LBS
Shipping Weight 3,000 LBS 4,100 LBS 5,000 LBS
Dimensions Given are Approximate
Width 33" 44"
Length 81" 102 3⁄4" 151 3⁄4" 156 3⁄4"
Height 105 1⁄4" 108 1⁄2" 111 3⁄4" 113 3⁄4"
Combustion Control Step modulation: Hi-Low-Off
Combustion System Proprietary forced draft, Pre-mixed burner
Ignition System Automatic Pilot burner
Power Supply 230, 460, or 575 V, 3 PHASE, 60 HZ
Max. Electrical Consumption 3.8 KVA 10.4 KVA 14.4 KVA
Fuel Type[3] Natural Gas or Propane Gas (3-5 PSIG)
Gas Consumption[4] 2,030 SCFH 4,070 SCFH 6,100 SCFH 7,120 SCFH
Gas Supply Pressure 3-5 PSIG Natural Gas or Propane Gas
Main Water Outlet 3" 4" 6"
Main Water Inlet 3" 4" 6"
Safety Valve Outlet 1" 1 1⁄2" 2"
Fuel Gas Inlet 1 1⁄2" 2"
Manual Blowdown 1 1⁄2"
Chimney Diameter (ID) 12" 14" 20"
Flame Detector Ultraviolet Flame Eye Sensor
Overheat Protection Low water cut off, Flow switch and Thermocouple
Max. Water Temperature 250°F
Full Water Content 44 GAL 64 GAL 90 GAL
Temperature Control Adjustable Temperature Controllers

NOTE:

i.  Fuel consumption is based on Natural Gas with a High heating value of 1,004 Btu/SCF.
ii. Efficiency is based on high heating values of fuels & operating at 140°F.

1. 49 BHP units available on request.
2. Thermal efficiencies are based on high heating values of fuels at 140°F supply temperature water.
3. UL and CGA/CSA approved for natural gas and propane.
4. Gas consumption based on natural gas with high heating value of 1004 BTU/SCF.

All Miura hot water boilers are fully packaged and test fired at the factory.

Built to meet or exceed UL and ASME standards in U.S.A.; CGA/CSA and B-51 standards in Canada.